GSME Hotspot Detector
Plants that are at risk of explosive dust must frequently be provided with explosion protection measures since ignition sources are often unavoidable. In addition to electrostatic phenomena and mechanically generated functions, the most frequent ignition sources particularly include glowing embers, open flames and hot surfaces. Alongside grounding monitoring systems and spark extinguishing systems, the Hotspot detector series make an enormous contribution to increasing explosion safety. The Hotspot series have been developed for the early identification of combustion reactions and thermal events, which can ultimately be ignition sources for explosions.
In contrast to conventional fire detection systems, the selection and positioning of special fire detectors is a particular challenge for industrial environments. The arrangement and alignment of the detectors should therefore be exclusively specified by specialist planners.
temperature of
the processed material.
Application
The Hotspot thermographic detector is specifically tailored for the early detection of hot surfaces and fire in dust-handling equipment, such as silos, dryers (excluding spray dryers), mills, conveyors or dust collectors.
Mechanism
Hotspots are freely parametrizable infrared camera systems in the form of detectors with integrated signal evaluation. In addition to process monitoring, they are also particularly suitable for the detection of overheating plant components and glowing embers.
Port
Unit

- Explosion prevention with early detection of smouldering and developing fires.
- Highest moisture and dust resistance with unique diffusion filter technology.
- Comprehensive explosion safety concepts through the integration of the detectors into the REMBE® EXKOP® Express control system.
Mechanical Properties
| Housing | Coated die-cast aluminium (corrosion-resistant) |
| Weight | 0.6 kg (without power cable) |
| Protection class | IP 64 |
| Explosion safety | Ex ta IIIC 105 °C Da (approval in accordance with ATEX and IECEx) |
Thermal Properties
| Relative humidity | 0 to 99 % relative humidity (non-condensing) |
| Temperature | -4 to +122 °F (-20 to +50 °C) |
Detection Properties
| Sensor combination | 32 x 31 Pixel |
| Viewing angle | 53° x 52° |
| Reaction time | 1 s |
| Time resolution | 0.1 s or 1 s (depending on the configuration) |
Electrical Properties
| Voltage supply | 20 to 40 V DC |
| Power consumption | 10 VA |
| Internal fuse protection | 750 mA |
| M-Bus Max. line length | ≈ 2 km |
| M-Bus Max. line capacity | ≈ 200 nF |
| M-Bus Baud rate | 4800 baud |
| Limit value contact alarm relay | 680 Ω , 20 mA max. (Alarm closer) |
| Limit value contact fault relay | 0 Ω, 40 V or 20 mA max. (Fault opener) |
Sealing Air
| Purity classes | Dust ≥ 2 — Water content ≥ 3 — Oil content ≥ 2 |
| Airflow rate | 200 to 300 l/h (poss. test necessary) |
- aerospace
- animal feed productions
- autoclaves
- condensers
- desalination plants
- dual-fuel engines
- elevators
- flare stacks
- food
- LNG
- mills and grinding plants
- reactors
- reverse osmosis systems
- separators
- silo
- water injection pumps

ATEX

IECEx
Recommended Resources
Hotspot Product Information
Loading 3D model…
HotSpot_SD_v002